11. Installation Instruction
11.1 Select the Best Location
11.1.1 Indoor Unit
Do not install the unit in excessive oil fume area
such as kitchen, workshop and etc.
There should not be any heat source or steam
near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Mount with the lowest moving parts at least 8ft
(2.4 m) above floor or grade level.
11.1.2 Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
Recommended installation height for outdoor unit
should be above the seasonal snow level.
Example: For XE9PKUA
If the unit is installed at 32.8 ft (10 m) distance, the
quantity of additional refrigerant should be 1.64 oz (50
g) .... (32.8 - 24.6) ft x 0.2 oz/ft = 1.64 oz. ((10-7.5) m
x 20 g/m = 50 g)
11.1.3 Indoor/Outdoor Unit Installation
Diagram
Vista de página 0
1 2 3 4 5 6 7 8

Resumo do Conteúdo

Página 1 - 11. Installation Instruction

24 11. Installation Instruction 11.1 Select the Best Location 11.1.1 Indoor Unit  Do not install the unit in excessive oil fume area such as kitche

Página 2 - 11.2 Indoor Unit

25 11.2 Indoor Unit The mounting wall shall be strong and solid enough to prevent it from vibration. Model Dimension c d e f g h XE9PKUA, XE12

Página 3

26 11.2.2 Indoor Unit Installation 11.2.2.1 For the right rear piping 11.2.2.2 For the right bottom piping 11.2.2.3 For the embedded piping

Página 5

28 11.2.3 Connect the Cable to the Indoor Unit 1 The inside and outside connection cable can be connected without removing the front grille. 2 Unsc

Página 6 - 11.3 Outdoor Unit

29 11.3 Outdoor Unit 11.3.1 Install the Outdoor Unit  After selecting the best location, start installation according to Indoor/Outdoor Unit Instal

Página 7

30 11.3.3 Evacuation of the Equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the followi

Página 8 - 11.3.5 Piping Insulation

31 9 Secure the wire onto the control board with the holder (clamper). 10 After completing wiring connections, reattach the particular plate and c