Panasonic U-52LE1U6 Ficha Técnica

Consulte online ou descarregue Ficha Técnica para Aparelhos de ar condicionado "split system" Panasonic U-52LE1U6. Panasonic U-52LE1U6 Data Sheet Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 2
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
ECO-i
Submittal Data
U-52LE1U6
Heat Pump: 52,000 btu VRF Outdoor Unit Previous Model Number: CHX05252
Approval:
Date:
Construction:
Unit#:
Drawing#:
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Capacities
Power
input
Ducted
Non-
Ducted
Mix
Cooling: Btu/h
4.57KW
51,500 52,000 51,750
SEER 14.6 17.4 16
Heating: Btu/h
4.58KW
57,500 58,500 58,000
HSPF 7.7 9.6 8.6
Cooling Mode Nominal Conditions
Indoor: °F DB/°F WB 80/67
Outdoor: °F DB 95
Pipe Length: Feet 25
Level Difference: Feet 0
Heating Mode Nominal Conditions
Indoor: °F DB 70
Outdoor: °F DB/°F WB 47/43
Pipe Length: Feet 25
Level Difference: Feet 0
Operating Range
Cooling: °F DB 14 to 113
Heating: °F WB -4 to 59
Compressor
Quantity/Type 1 Inverter Driven Rotary
Capacity Control Range: % 10 - 100
Fan
Quantity/Type 2 Propeller
Fan Motor Output: W 90
Power Supply
V/PH/Hz. 208 - 230/1/60
Minimum Circuits Amps
(MCA):Amps
29
Max. Overcurrent Protection
(MOCP)
50
Weight
Weight: (lbs) 229
Compressor Warranty: Six Years
Parts Warranty: One Year
Salt Protection also available
Data is subject to change
External Finish: Electrostatic Powder Coating
Sound Data: Sound Pressure Level 51 dB (A)
Refrigerant
Refrigerant Type 410A
Coil
Coil Face Area: (sq. ft.) 11.7
Number of Rows 3
Protection Devices
High Pressure Switch Yes
Overcurrent (CT Method) Yes
Crankcase Heaters: (W) 30
Data is Subject to Change.
Vista de página 0
1 2

Resumo do Conteúdo

Página 1 - Submittal Data

ECO-i™ Submittal DataU-52LE1U6 Heat Pump: 52,000 btu VRF Outdoor Unit Previous Model Number: CHX05252Approval:Date:Construction:Unit#:Drawing#:Job

Página 2 - Dimensions

Panasonic North AmericaAir Conditioning Division1690 Roberts Blvd., NW, Suite 110Kennesaw, GA 30144http://www.panasonic.com/airconDimensions

Comentários a estes Manuais

Sem comentários