Panasonic S18NKUA Manual de Serviço

Consulte online ou descarregue Manual de Serviço para Aparelhos de ar condicionado "split system" Panasonic S18NKUA. Panasonic S18NKUA Service Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 0
© Panasonic Appliances Air-Conditioning Malaysia
Sdn. Bhd. 2012. Unauthorized copying and distribution
is a violation of law.
Order No: PAPAMY1204086CE
Indoor Unit Outdoor Unit
CS-S18NKUA
CS-S24NKUA
CU-S18NKUA
CU-S24NKUA
TABLE OF CONTENTS
1. Safety Precautions.............................................3
2. Specification .......................................................5
3. Location of Controls and Components ...........7
3.1 Indoor Unit....................................................7
3.2 Outdoor Unit.................................................7
3.3 Remote Control ............................................7
4. Dimensions.........................................................8
4.1 Indoor Unit....................................................8
4.2 Outdoor Unit.................................................9
5. Refrigeration Cycle Diagram...........................10
6. Block Diagram ..................................................11
7. Wiring Connection Diagram............................12
7.1 Indoor Unit..................................................12
7.2 Outdoor Unit...............................................13
8. Electronic Circuit Diagram ..............................14
8.1 Indoor Unit..................................................14
8.2 Outdoor Unit...............................................15
9. Printed Circuit Board .......................................16
9.1 Indoor Unit..................................................16
9.2 Outdoor Unit ...............................................18
10. Installation Instruction.....................................19
11. Operation Control.............................................27
11.1 Basic Function............................................27
11.2 Indoor Fan Motor Operation.......................28
11.3 Outdoor Fan Motor Operation ....................28
11.4 Airflow Direction .........................................28
11.5 Quiet Operation (Cooling Mode/Cooling Area
of Dry Mode)...............................................29
11.6 Powerful Mode Operation ..........................30
11.7 Timer Control..............................................30
11.8 Random Auto Restart Control ....................30
11.9 Indication Panel..........................................31
12. Protection Control............................................32
12.1 Restart Control (Time Delay Safety Control) .
....................................................................32
12.2 30 Seconds Forced Operation ...................32
12.3 Total Running Current Control ...................32
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the products dealt with in this service information by anyone else could result in serious injury or death.
Vista de página 0
1 2 3 4 5 6 ... 71 72

Resumo do Conteúdo

Página 1

© Panasonic Appliances Air-Conditioning Malaysia Sdn. Bhd. 2012. Unauthorized copying and distribution is a violation of law. Order No: PAPAMY1204086

Página 2

10 5. Refrigeration Cycle Diagram

Página 4

12 7. Wiring Connection Diagram 7.1 Indoor Unit

Página 5 - 2. Specification

13 7.2 Outdoor Unit

Página 6

14 8. Electronic Circuit Diagram 8.1 Indoor Unit

Página 8 - 4. Dimensions

16 9. Printed Circuit Board 9.1 Indoor Unit 9.1.1 Main Printed Circuit Board

Página 9 - 4.2 Outdoor Unit

17 9.1.2 Power Printed Circuit Board 9.1.3 Indicator Printed Circuit Board

Página 10

18 9.2 Outdoor Unit 9.2.1 Main Printed Circuit Board

Página 11 - 6. Block Diagram

19 10. Installation Instruction • IMPORTANT (only for S18NKUA) This product has been designed and manufactured to meet ENERGY STAR® criteria for ener

Página 12 - 7. Wiring Connection Diagram

2 12.4 IPM (Power Transistor) Prevention Control ... ...32 12.5 Compressor Overheat

Página 13 - 7.2 Outdoor Unit

20 10.1.3 Indoor Unit 10.1.3.1 How to Fix Installation Plate The mounting wall must be strong and solid enough to prevent if from the vibration.

Página 14 - 8.1 Indoor Unit

21 10.1.3.3 Indoor Unit Installation 10.1.3.4 For the right rear piping 10.1.3.5 For the right bottom piping 10.1.3.6 For the embedded piping

Página 15 - 8.2 Outdoor Unit

22 10.1.3.7 Connect the Cable to the Indoor Unit 1. The inside and outside connecting cable can be connected without removing the front grille. 2

Página 16 - 9. Printed Circuit Board

23 10.1.3.8 Wire Stripping and connecting requirement 10.1.3.9 Cutting and flaring the piping 1 Please cut using pipe cutter and then remove the

Página 17

24 10.1.4 Outdoor Unit 10.1.4.1 Install the Outdoor Unit • After selecting the best location, start installation to INDOOR/OUTDOOR UNIT INSTALLATION

Página 18 - 9.2 Outdoor Unit

25 10.1.4.3 Evacuation of the equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the follo

Página 19 - 10. Installation Instruction

26 9. Secure the wire onto the control board with the holder (clamper). 10. After completing wiring connections, reattach the particular plate and

Página 20 - 10.1.3 Indoor Unit

27 11. Operation Control 11.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operation mode as

Página 21

28 11.2 Indoor Fan Motor Operation 11.2.1 Basic Rotation Speed • Manual Fan Speed o Fan motor’s number of rotation is determined according to remot

Página 22

29 11.4.1 Vertical Airflow Vane Angle (°) Operation Mode Airflow Direction 1 2 3 4 5 Auto 20 ~ 45 Cooling Manual 20 26 32 37 45 Auto 20 ~ 45 Soft

Página 23

3 1. Safety Precautions • Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. • Electrical work must be installed or ser

Página 24

30  During quiet operation, if ON timer activates, quiet operation maintains.  After off, when on back, quiet operation is not memorized. • Contr

Página 25

31 11.9 Indication Panel LED POWER TIMER QUIET POWERFUL Color Green Orange Orange Orange Light ON Operation ON Timer Setting ON Quiet Mode

Página 26 - 10.1.4.5 Piping Insulation

32 12. Protection Control 12.1 Restart Control (Time Delay Safety Control) • The compressor will not turn on within 3 minutes from the moment oper

Página 27 - 11. Operation Control

33 12.5 Compressor Overheating Prevention Control • Instructed frequency for compressor operation will be regulated by compressor discharge tempe

Página 28 - 11.4 Airflow Direction

34 12.10 Cooling Overload Control • Pipe temperature limitation / restriction. o Detects the outdoor pipe temperature and carry out restriction /

Página 29 - 11.4.2 Horizontal Airflow

35 13. Servicing Mode 13.1 Auto Off/On Button Auto OFF/ON Button Pressed Auto OFF/ON Button Pressed 5 sec Auto Operation Test Run Operation (

Página 30 - 11.7 Timer Control

36 13.2 Remote Control Button 13.2.1 SET Button • To check remote control transmission code and store the transmission code to EEPROM o Press “Set”

Página 31 - 11.9 Indication Panel

37 14. Troubleshooting Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical pr

Página 32 - 12. Protection Control

38 14.1.1 Relationship between the condition of the air conditioner and pressure and electric current Cooling Mode Condition of the air conditioner

Página 33

39 14.2 Breakdown Self Diagnosis Function 14.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code) • Once error occurred during operation, t

Página 34

4 WARNING 19. During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrig

Página 35 - 13. Servicing Mode

40 14.3 Error Code Table Diagnosis display Abnormality / Protection control Abnormality JudgmentEmergency Operation Primary location to verify H00

Página 36 - 13.2 Remote Control Button

41 14.4 Troubleshooting Flowchart 14.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions • During startup and operation

Página 37 - 14. Troubleshooting Guide

42 14.4.2 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heati

Página 38

43 14.4.3 H16 (Outdoor Current Transformer Open Circuit) Malfunction Decision Conditions • A current transformer (CT) is detected by checking the co

Página 39 - 14.2.2 To Make a Diagnosis

44 14.4.4 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions • The rotation speed detected by the Hall IC during fan

Página 40 - 14.3 Error Code Table

45 14.4.5 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, th

Página 41

46 14.4.6 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating, th

Página 42

47 14.4.7 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and heating,

Página 43

48 14.4.8 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions • During startup and operation of cooling and he

Página 44

49 14.4.9 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions • The supply power is detected for its requirement

Página 45

5 2. Specification Indoor CS-S18NKUA CS-S24NKUA Model Outdoor CU-S18NKUA CU-S24NKUA Performance Test Condition AHRI AHRI Phase, Hz Single, 60 Si

Página 46

50 14.4.10 H98 (Indoor High Pressure Protection) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Condit

Página 47

51 14.4.11 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Malfunction Decision Conditions • Freeze prevention control takes place

Página 48

52 14.4.12 F11 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions • When cooling operation, when indoor pipe temperature

Página 49

53 14.4.13 F90 (Power Factor Correction Protection) Malfunction Decision Conditions • During startup and operation of cooling and heating, when Po

Página 50

54 14.4.14 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions • During cooling, compressor frequency = Fcmax. • During cooling

Página 51

55 14.4.15 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor r

Página 52

56 14.4.16 F95 (Cooling High Pressure Abnormality) Malfunction Decision Conditions During operation of cooling, when outdoor unit heat exchanger hi

Página 53

57 14.4.17 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (212°F) is dete

Página 54

58 14.4.18 F97 (Compressor Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature d

Página 55

59 14.4.19 F98 (Input Over Current Detection) Malfunction Decision Conditions During cooling and heating operation, when an input over-current (16.

Página 56

6 Indoor CS-S18NKUA CS-S24NKUA Model Outdoor CU-S18NKUA CU-S24NKUA Control Device Expansion Valve Expansion Valve Refrigerant Oil cm3 FV50S (8

Página 57

60 14.4.20 F99 (Output Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an output over-current

Página 58

61 WARNING 15. Disassembly and Assembly Instructions High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capa

Página 59

62 15.1.1.2 To remove discharge grille

Página 60 - Abnormal resistance 0 or ∞

63 15.1.1.3 To remove control board 15.1.1.4 To remove cross flow fan and indoor fan motor

Página 62

65 16. Technical Data 16.1 Operation Characteristics 16.1.1 CS-S18NKUA CU-S18NKUA • Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT

Página 63

66 • Piping Length Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F

Página 64

67 16.1.2 CS-S24NKUA CU-S24NKUA • Cooling Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Piping

Página 65 - 16. Technical Data

68 • Piping Length Characteristic o Room temperature: 81°F (DBT), 66°F (WBT) o Operation condition: High fan speed o Outdoor temperature: 95°F

Página 66

69 17. Exploded View and Replacement Parts List 17.1 Indoor Unit Note The above exploded view is for the purpose of parts disassembly and replacemen

Página 67 - 16.1.2 CS-S24NKUA CU-S24NKUA

7 3. Location of Controls and Components 3.1 Indoor Unit 3.2 Outdoor Unit 3.3 Remote Control

Página 68

70 REF. NO. PART NAME & DESCRIPTION QTY. CS-S18NKUA CS-S24NKUA REMARK 1 CHASSIS COMPLETE 1 CWD50C1637 ← 2 FAN MOTOR 1 ARW7663AC ← O 3

Página 69 - 17.1 Indoor Unit

71 17.2 Outdoor Unit Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as s

Página 70

72 REF. NO. PART NAME & DESCRIPTION QTY. CU-S18NKUA CU-S24NKUA REMARK 1 CHASSIS COMPLETE 1 CWD52K1229A ← 2 ANTI - VIBRATION BUSHING 3

Página 71 - 17.2 Outdoor Unit

8 4. Dimensions 4.1 Indoor Unit

Página 72

9 4.2 Outdoor Unit

Comentários a estes Manuais