Product description
System example for ECOi single-connection system
ECOi or ECO G Air Handling Unit
I/D-O/D
wiring
Wiring for Thermostat
& Solenoid Valve
Piping
Air Handling Unit Kit
PAW-280MAH2
Multi-connection system
Note:
The following restrictions apply only if PAW-560MAH2(L) is used alone or in combination with other AHU Kits. For all
other AHU Kits and AHU Kit combinations without PAW-560MAH2(L) no such restrictions apply.
1 All AHU heat exchangers belonging to the same refrigerant circuit have to be installed in the same chassis equipped
with one single fan motor.
2 One AHU Kit and correspondingly one magnetic relay is required for each heat exchanger. All AHU Kits have to be
wired to the fan motor.
3 All AHU Kits shall be connected and controlled by group control wiring of remote controller.