INSTALLATION INSTRUCTIONS
VRF System Air Conditioner
This air conditioner uses the refrigerant R410A.
NOTE
External diameter of service port R410A: 5/16"
Model No.
Indoor Units
Type Indoor Unit Type 7 9 12 15 18 19 24 36 48 54
U1 4-Way Cassette
S-12MU1U6
(CZ-36KPU2U)**
S-18MU1U6
(CZ-36KPU2U)**
S-24MU1U6
(CZ-36KPU2U)**
S-36MU1U6
(CZ-36KPU2U)**
Y1
4-Way Cassette
60 × 60
S-12MY1U6
(CZ-18KPY1U)**
S-18MY1U6
(CZ-18KPY1U)**
D1 1-Way Cassette
S-07MD1U6
(CZ-12KPD1U)**
S-09MD1U6
(CZ-12KPD1U)**
S-12MD1U6
(CZ-12KPD1U)**
F1
Low Silhouette
Ducted
S-07MF1U6 S-09MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6 S-24MF1U6 S-36MF1U6 S-48MF1U6 S-54MF1U6
M1
Slim Low Static
Ducted
S-07MM1U6 S-09MM1U6 S-12MM1U6 S-15MM1U6 S-18MM1U6
E1
High Static
Pressure Ducted
S-36ME1U6 S-48ME1U6
T1 Ceiling
S-12MT1U6 S-18MT1U6 S-24MT1U6
K1 Wall Mounted
S-07MK1U6 S-09MK1U6 S-12MK1U6 S-18MK1U6 S-19MS1U6* S-24MK1U6
P1 Floor Standing
S-07MP1U6 S-09MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6 S-24MP1U6
R1
Concealed Floor
Standing
S-07MR1U6 S-09MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6 S-24MR1U6
* Necessary to install the External Electronic Expansion Valve Kit (Optional : CZ-P56SVK1U)
** Panel (optional parts)
Optional Controllers
RC
Timer Remote Controller CZ-RTC2
Wireless Remote Controller (For F1, M1, E1, P1, R1 Types) CZ-RWSC1U
Wireless Remote Controller (For U1 Type) CZ-RWSU1U
Wireless Remote Controller (For Y1 Type) CZ-RWSY1U
Wireless Remote Controller (For D1, T1 Types) CZ-RWST1U
Wireless Remote Controller (For K1 Type) CZ-RWSK1U
Simplifi ed Remote Controller CZ-RE2C2
System Controller CZ-64ESMC1U
Schedule Timer CZ-ESWC2
Intelligent Controller CZ-256ESMC1U
Communication Adaptor CZ-CFUNC1U
Remote Sensor CZ-CSRC2
LonWorks Interface CZ-CLNC1U
85464369530011 CV6233187013
VRF_Indoor_US.indb 1VRF_Indoor_US.indb 1 2011/09/30 12:22:532011/09/30 12:22:53
Vista de página 0
1 2 3 4 5 6 ... 83 84

Resumo do Conteúdo

Página 1 - INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONSVRF System Air ConditionerThis air conditioner uses the refrigerant R410A.NOTE External diameter of service port R410A: 5/16&

Página 2 - Please Read Before Starting

103. HOW TO INSTALL THE INDOOR UNIT4-Way Cassette Type (U1 Type) 3-1. Preparation for SuspendingThis unit uses a drain pump. Use a level gauge to ch

Página 3 - Check of Density Limit

11(2) The length of suspension bolts must be appropriate for a distance between the bottom of the bolt and the bottom of the unit of more than 19/32&q

Página 4 - CONTENTS

12CAUTIONIn cases where it is necessary to raise the height ●of the drain piping, the drain piping can be raised to a maximum height of 33-15/32"

Página 5 - 1. GENERAL

133-6. How to Install the Ceiling Panel3-6-1. Before Installing the Ceiling PanelChecking the unit position(1) Check that the ceiling hole is within

Página 6 - Table 1-2 (1-Way Cassette)

143-6-2. Installing the Ceiling PanelAfter completing the wiring process, install the supplied wiring cover before installing the panel.It is not pos

Página 7 - Table 1-6 (Wall Mounted)

153-6-3. Wiring the Ceiling Panel(1) Open the cover of the electrical component box. (2) Connect the 7P wiring connector (red) from the ceiling panel

Página 8

163-6-5. Checking After InstallationCheck that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling

Página 9 - Min.8 ft

174-Way Cassette 60 × 60 Type (Y1 Type) 3-8. Preparation for SuspendingThis unit uses a drain pump. Use a level gauge to check that the unit is level

Página 10 - (field supply)

18CAUTIONAttach so that the hose band ●fastener is on the side of the drain port.Attach the hose bands so that ●each is approximately 13/64" to

Página 11 - Unit: in. (mm)

193-12. Checking the DrainageAfter wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For

Página 12 - Support

2IMPORTANT! Please Read Before StartingThis air conditioning system meets strict safety and operating standards. As the installer or service person, i

Página 13 - Ceiling side

20CAUTIONIf the screws are not suffi ciently ●tightened, trouble such as that shown in the fi gure below may occur. Be sure to tighten the screws secur

Página 14 - Condensation, water leakage

213-13-5. Checking After InstallationCheck that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceilin

Página 15 - Mains side

221-Way Cassette Type (D1 Type) 3-14. Suspending the Indoor Unit(1) Follow the diagrams to make the holes in the ceiling. (Figs. 3-52 and 3-53)(2) De

Página 16

233-15. Placing the Unit Inside the CeilingCAUTIONBe sure to use a level gauge and confi rm that the unit is level. If it is not level, water leakage m

Página 17

242-1/8 19/32 19/32 2-1/8 Suspension bolts Suspension boltsTubing side Unit: in.Fig. 3-6025/32 25/32 25/32 CeilingmaterialFig. 3-61Drainage check sect

Página 18

25CAUTIONDo not install an air bleeder as this may cause water to ●spray from the drain pipe outlet. (Fig. 3-64)In cases where it is necessary to rai

Página 19

263-18. Electrical Power Wiring(1) Wiring connectionsThe power inlet is on the side of the indoor unit where the refrigerant tubing is located. The el

Página 20

27Removing the intake grilleSlide the intake grille hooks (2 locations) in the direction of the arrow to open the intake grille. (Fig. 3-72)When the i

Página 21

28(5) Align the installation holes on the panel with the bolt holes on the unit.(6) Insert the supplied washer head bolts into the 4 panel installatio

Página 22

293-19-3. Wiring the ceiling panel(1) Loosen the 2 screws on the electrical component box lid, and remove the lid. (Fig. 3-80)(2) Fasten the wiring c

Página 23

3When ServicingTurn the power OFF at the main power box (mains) • before opening the unit to check or repair electrical parts and wiring.Keep your fi n

Página 24 - Drain insulator (supplied)

30Fig. 3-84Indoor unit Inspection access 17-23/3217-23/32Air outlet duct flange Min. 9-27/32Min. 15-3/4Min. 25-19/3222-27/32 A (Suspension bolt pitch)

Página 25

313-21. Suspending the Indoor UnitDepending on the ceiling type:• Insert suspension bolts as shown in Fig. 3-86 or• Use existing ceiling supports or

Página 26

323-22. Installing the Drain Piping(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the drain and use the supplied hose band to prevent water

Página 27

33CAUTIONBe careful since the fan will start when you short the pin on the indoor control board.(4) When the check of drainage is complete, open the c

Página 28

343-25. When Installing the Indoor UnitConfi rm that the indoor unit should be installed in a horizontal position.Use the level gauge or vinyl tube and

Página 29

35Slim Low Static Ducted Type (M1 Type) 3-27. Required Minimum Space for Installation and ServiceThis air conditioner is usually installed above the

Página 30 - No. of holes

36A2.32.7Unit: ft.(Inspection access)Arrow view A Inspection access (Field supply)CeilingAir intakeAir discharge3-28. Preparations Before Installation

Página 31

373-30. Installing the DuctConnect the duct supplied in the fi eld.Air inlet sideAttach the duct and intake-side fl ange (fi eld supply). ●Connect the fl

Página 32 - Support pieces

383-31. Suspending the Indoor UnitDepending on the ceiling type:• Insert suspension bolts as shown in the diagram or• Use existing ceiling supports

Página 33 - Power supply outlet

393-32. Installing the Drain Piping(1) Prepare standard hard PVC pipe (O.D. 1-1/32") for the drain and use the supplied hose band to prevent wate

Página 34

4IMPORTANT! ...2Please Read Before StartingCheck of Density Limit1. GENERAL ...

Página 35

40177 353177 353Airflow (CFM) Airflow (CFM)Airflow (CFM) Airflow (CFM)Airflow (CFM)S-09MM1U6S-07MM1U6Airflow (CFM)External Static Pressure (in.WG)Exte

Página 36

41High Static Pressure Ducted Type (E1 Type) 3-35. Required Minimum Space for Installation and ServiceThis air conditioner is usually installed abov

Página 37

423-36. Suspending the Indoor UnitDepending on the ceiling type:Insert suspension bolts as shown in Fig. 3-120 ●orUse existing ceiling supports or con

Página 38

43Sealing tape Drain joint (supplied) Drain pan Drain opening (25A or 1-11/32" male screw) Fig. 3-123Good Min. 1/100 Downward gradient Not good F

Página 39

44Ceiling Type (T1 Type) 3-40. Required Minimum Space for Installation and Service(1) Dimensions of suspension bolt pitch and unitTable 3-6Unit: in.D

Página 40 - Indoor control board

453-41. Suspending the Indoor Unit(1) Place the full-scale diagram (supplied) on the ceiling at the spot where you want to install the indoor unit. Us

Página 41

46(5) Before suspending the indoor unit, remove the 2 or 3 screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing

Página 42

47CAUTIONAttach so that the hose band fastener is ●on the side of the drain port. Attach the hose bands so that each is ●approximately 13/64 – 63/64

Página 43 - H: At shipment

48Never allow traps to occur in the course of the piping. ●Insulate any piping inside the room to prevent dripping. ●After the drain piping, pour wate

Página 44

49Wall Mounted Type (K1 Type) 3-45. Removing the Rear Panel from the Unit(1) Remove the set screws used to fasten the rear panel to the indoor unit d

Página 45 - Ceiling suppor t

51. GENERALThis booklet briefl y outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the

Página 46 - Approx

503-47. Installing the Rear Panel onto the WallConfi rm that the wall is strong enough to support the unit. See either Item a) or b) below depending on

Página 47 - Rear outlet port

513-49. Preparing the Tubing(1) Arrangement of tubing by directionsa) Right or left tubingThe corner of the right or left frame should be cut with a h

Página 48 - 63/64 63/64

523-50. Shaping the TubingRight-rear tubing(1) Shape the refrigerant tubing so that it can easily go into the hole. (Fig. 3-166)(2) After performing a

Página 49

533-52. When Using Wireless Remote Controller Instead of Wired Remote ControllerWhen the wireless remote controller is to be used, slide the switch on

Página 50

543-53. External Electronic Expansion Valve Kit (CZ-P56SVK1U)Precautions in this manual are given in the form of “Warnings” or “Cautions.” Both types

Página 51

553. Cutting and Flaring of Liquid TubeAfter determining the position for installation, cut the liquid tube and fl are the connecting portion. (Pay att

Página 52

565. Flare Insulation of TubingAfter completing a leakage test, apply heat insulation. (Fig. 3-191)* Use the fl are insulator provided with the product

Página 53

577. Wiring ProcedureWARNINGBe sure to turn the power off at the mains before removing or connecting connectors to avoid electric shock hazard.Connect

Página 54

58Floor Standing Type (P1 Type) Concealed Floor Standing Type (R1 Type)3-54. Required Minimum Space for Installation and ServiceInstall the unit whe

Página 55 - MUST BE INSTALLED AS ARROWS

59Unit: in.LengthTypeABCDEFLiquidtubeGastube7, 9, 12 35-19/32 27-1/4 26-29/64 26-3/16 19-11/16 3-25/64Ø1/4 Ø1/215, 1847-63/64 39-41/64 39-29/64 38-37/

Página 56 - Liquid tube

6Table 1-1 (4-Way Cassette)Part Name Figure Q’ty RemarksFull-scale installation diagram 1 Printed on container boxDrain hose1 For securing drain hose

Página 57

603-56. Removing and Attaching the Front Panel (Floor Standing Type)NOTEA dew-prevention heater is secured behind the front panel.When removing or att

Página 58 - Horizontal view Vertical view

61CAUTIONInsulate both gas and liquidtubes.To insulate tubes ●(1) Wrap the fl are nuts with the supplied white insulating tape.(2) Wrap the fl are nuts

Página 59

62SUPPLEMENT ON DRAIN PIPING 1. Drain hose installationDrain portIndoor unitIndoor unitDrain port may possibly be damaged if PVC adhesive is used.*

Página 60 - Front panel

634. ELECTRICAL WIRING 4-1. General Precautions on Wiring (1) Before wiring, confi rm the rated voltage of the unit as shown on its nameplate, then car

Página 61

644-3. Wiring System Diagram****212121BCAL1L2L1L2L1L2L1L221ABAAU2U1L2L1R2R1U2U1L2L1R2R1U2U1L2L1R2R1U2U1L2L121B13RC(BLU)WHTBLKWHTBLKWHTBLKWHTBLK208 / 2

Página 62

65(1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the ou

Página 63 - 4. ELECTRICAL WIRING

66CAUTIONLoose wiring may cause the terminal to overheat or result in unit malfunction. A fi re hazard may also exist. Therefore, ensure that all wirin

Página 64 - L1 L2 U1 U2 R1 R2

Clamping clipTwistEarth screwPower wiring (fi eld supplied)Connection for Solenoid Valve Kit (for 3WAY)Remote control wiring and Inter-unit control wir

Página 65

68Important Note When Wiring for Common Type (Continued)Remote control wiring and Inter-unit control wiring (fi eld supplied)E1 TypeM1 TypeT1 TypeP1, R

Página 66

69Important Note When Wiring for Common Type (Continued)K1 TypeK1 TypeConduit(fi eld supplied)Model : S-07MK1U6S-09MK1U6S-12MK1U6Power wiring (fi eld s

Página 67 - F1 TypeD1 Type

7Table 1-4 (High Static Pressure Ducted)Part Name Figure Q’ty RemarksWasher8 For suspending indoor unit from ceilingNut8 For suspending indoor unit f

Página 68 - P1, R1 Type

704-5. Important Note When Wiring for Y1 TypeConnect the wires referring to the diagram.Note that the control wirings (Low Voltages) shall be segregat

Página 69

715. HOW TO PROCESS TUBINGThe liquid tubing side is connected by a fl are nut, and the gas tubing side is connected by brazing.5-1. Connecting the Ref

Página 70

72Caution Before Connecting Tubes Tightly(1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are

Página 71 - 5. HOW TO PROCESS TUBING

735-3. Insulating the Refrigerant TubingTubing InsulationThermal insulation must be applied to all unit tubing, ●including the distribution joint (pu

Página 72 - Flare nut

74ClampDrain horseInsulated tubesFig. 5-10Apply putty hereTubingFig. 5-115-4. Taping the Tubes(1) At this time, the refrigerant tubes (and electrical

Página 73

756. APPENDIXNAME OF PARTS 4-Way Cassette (U1) 4-Way Cassette 60 × 60 (Y1)Water drain Ceiling panel (optional) Air outlet (4 locations) Air intake g

Página 74 - Apply putty here

76Care and Cleaning WARNING1. For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning.2. Do not pour w

Página 75 - 6. APPENDIX

77Care and Cleaning (continued) How to remove the fi lter4-Way Cassette (U1):4-way Cassette 60 × 60 (Y1):1. Use a screwdriver to remove the bolt scre

Página 76 - Two weeks Two weeks

78Care and Cleaning (continued) How to remove the fi lter(continued)Ceiling (T1): 1. Take hold of the fi nger-hold on the air intake grille and press

Página 77

79Care and Cleaning (continued) How to remove the filter(continued)Floor Standing (P1):Concealed Floor Standing (R1):1. Remove the screw at the bott

Página 78

8Table 1-8 (Slim Low Static Ducted)Part Name Figure Q’ty RemarksWasher8 For suspension fi ttingFlare insulation T3T52 set For gas / liquid tube con

Página 79

80CAUTION1. Certain metal edges and the condenser fi ns are sharp and may cause injury if handled improperly; special care should be taken when you cl

Página 80

81Troubleshooting If your air conditioner does not work properly, fi rst check the following points before requesting service. If it still does not wo

Página 81

82VRF_Indoor_US.indb 82VRF_Indoor_US.indb 82 2011/09/30 12:23:152011/09/30 12:23:15

Página 82

83VRF_Indoor_US.indb 83VRF_Indoor_US.indb 83 2011/09/30 12:23:152011/09/30 12:23:15

Página 83

DC0811-10911Printed in JapanVRF_Indoor_US.indb 84VRF_Indoor_US.indb 84 2011/09/30 12:23:152011/09/30 12:23:15

Página 84 - Printed in Japan

92. SELECTING THE INSTALLATION SITE2-1. Indoor UnitAVOID:areas where leakage of fl ammable gas may be expected. ●places where large amounts of oil mis