Order No: PHAAM1111120A1
Outdoor Unit
CU-2E18NBU
Please file and use this manual together with the service manual for Model No. CS-E9NKUAW CS-E12NKUAW, Order No.
PHAAM1111087C1.
TABLE OF CONTENTS
1. Safety Precautions.............................................3
2. Specifications.....................................................5
2.1 CU-2E18NBU...............................................5
3. Dimensions.........................................................8
4. Refrigeration Cycle Diagram.............................9
5. Block Diagram ..................................................10
6. Wiring Connection Diagram............................11
7. Electronic Circuit Diagram ..............................12
8. Printed Circuit Board .......................................13
8.1 Main Printed Circuit Board .........................13
8.2 Noise Filter Printed Circuit Board...............14
8.3 Display Printed Circuit Board .....................14
9. Installation Information ...................................15
9.1 Check Points ..............................................15
10. Installation Instruction.....................................16
10.1 Select The Best Location ...........................16
10.2 Install The Outdoor Unit .............................17
10.3 Connect the Piping.....................................17
10.4 Evacuation of the Equipment .....................18
10.5 Connect The Cable To The Outdoor
Unit .............................................................19
10.6 Heat Insulation ...........................................19
11. Operation Control.............................................20
11.1 Cooling Operation ......................................20
11.2 Heating Operation ......................................21
12. Simultaneous Operation Control....................22
13. Protection Control............................................23
13.1 Freeze Prevention control (Cool) ...............23
13.2 Dew Prevention control (Cool) ...................23
13.3 Electronic Parts Temperature Rise
Protection 1 (Cool) .....................................23
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the product or products dealt with in this service information by anyone else could result in serious injury or death.
Vista de página 0
1 2 3 4 5 6 ... 56 57

Resumo do Conteúdo

Página 1 - TABLE OF CONTENTS

© Panasonic HA Air-Conditioning (M) Sdn. Bhd. 2011. Unauthorized copying and distribution is a violation of law. Order No: PHAAM1111120A1 Outdoor U

Página 2

10 5. Block Diagram

Página 3 - 1. Safety Precautions

11 6. Wiring Connection Diagram

Página 4

12 7. Electronic Circuit Diagram

Página 5 - 2. Specifications

13 8. Printed Circuit Board 8.1 Main Printed Circuit Board

Página 6 - •” : Available

14 8.2 Noise Filter Printed Circuit Board 8.3 Display Printed Circuit Board

Página 7

15 9. Installation Information 9.1 Check Points QUICK GUIDE PIPING AND ELECTRICAL SPECIFICATION Piping size Indoor (ID) & Outdoor (OD) units: Po

Página 8 - 3. Dimensions

16 10. Installation Instruction10.1 Select The Best Location 10.1.1 Outdoor Unit  If an awning is built over the unit to prevent direct sunlight or

Página 9

17 Outdoor Unit Installation Guidelines  Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the insta

Página 10 - 5. Block Diagram

18 CUTTING AND FLARING THE PIPING 1 Please cut using pipe cutter and then remove the burrs. 2 Remove the burrs by using reamer. If burrs is not remo

Página 11 - 6. Wiring Connection Diagram

19 10.5 Connect The Cable To The Outdoor Unit 1 Remove Control Board Cover (Metal) by loosening 2 screws. 2 Remove Valve Cover (Metal) by loosening

Página 12

2 13.4 Electronic Parts Temperature Rise Protection 2 (Cool)...23 13.5 Cooling overload control (Cool)...

Página 13 - 8. Printed Circuit Board

20 11. Operation Control 11.1 Cooling Operation 11.1.1 Outdoor fan control  When cooling operation is enabled, based on outdoor ambient temperature

Página 14

21 11.2 Heating Operation 11.2.1 Outdoor fan control  When heating operation is enabled, based on outdoor ambient temperature, fan motor control wi

Página 15 - 9. Installation Information

22 12. Simultaneous Operation Control 1 Operation modes which can be selected using the remote control unit: Automatic, Cooling, Soft Dry, Heating,

Página 16 - 10. Installation Instruction

23 13. Protection Control 13.1 Freeze Prevention control (Cool)  When received freeze prevention signal from indoor unit, the compressor frequency

Página 17 - 10.3 Connect the Piping

24 13.5 Cooling overload control (Cool)  This control detect outdoor pipe temperature and perform the compressor frequency restriction during cooli

Página 18

25 13.8 Deice Control  When outdoor pipe temperature and outdoor air temperature is low, deice operation starts where indoor fan motor and outdoor f

Página 19 - 10.6 Heat Insulation

26 13.13 Compressor Protection Control (Gas leak detection control 1)  Control start conditions o For 5 minutes, the compressor continuously oper

Página 20 - 11. Operation Control

27 14. Servicing Mode 14.1 CU-2E18NBU 14.1.1 Pump down operation (SW1)  Operate the pump down process according to the following procedure o Con

Página 21 - 11.2 Heating Operation

28 14.1.3 Wiring Error check  The unit capable to correct the wiring error automatically by following procedures. o Confirm the valve on the liqui

Página 22

29 15. Troubleshooting Guide 15.1 Self Diagnosis Function  The display screen of wireless remote control unit and the self-diagnosis LEDs (green) o

Página 23 - 13. Protection Control

3 CAUTION WARNING WARNING 1. Safety Precautions  Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.  Electrical work

Página 26

32 WARNING 16. Disassembly and Assembly Instructions High Voltage are generated in the electrical parts area by the capacitor. Ensure that the cap

Página 27 - 14. Servicing Mode

33 16.1.3 Removing the Control P.C. Board 6 Remove the drip proof cover. 7 Disconnect the connectors (lead wires of the compressor, sensor

Página 28 - 14.1.4 Power Save Mode

34 3 Disconnect the fan motor connector from the control P.C. Board. 4 Loosen the 4 fan motor mounting screws then remove the fan motor.

Página 29 - 15. Troubleshooting Guide

35 17. Technical Data 17.1 Operation Characteristics 17.1.1 One Indoor Unit Operation  Cooling Characteristic [Condition] Room temperature: 81°F

Página 30

36  Cooling Characteristic [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Piping Length: 24.6ft Comp

Página 31

37  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Página 32

38  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Página 33

39  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Página 34

4 CAUTION 18. For R410A models, when connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnorm

Página 35 - 17. Technical Data

40  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Página 36 -  Cooling Characteristic

41  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Página 37

42  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Página 38

43 17.1.2 Two Indoor Unit Operation  Cooling Characteristic [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan s

Página 39 -  Heating Characteristic

44  Cooling Characteristic [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Piping Length: 24.6ft Comp

Página 40

45  Cooling Characteristic [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Piping Length: 24.6ft Comp

Página 41

46  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Página 42

47  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Página 43

48  Piping Length Characteristic Cooling [Condition] Room temperature: 81°F (DBT), 66°F (WBT) Operation condition: High fan speed Outdoor tempe

Página 44

49  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Página 45

5 2. Specifications 2.1 CU-2E18NBU Item Unit OUTDOOR UNIT Indoor Unit Combination 3.2kW + 3.2kW Power Source 1 Phase, 208 – 230V, 60Hz (Power

Página 46

50  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Página 47

51  Heating Characteristic [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Piping Length: 24.6ft Compressor Freq:

Página 48

52  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Página 49

53  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Página 50

54  Piping Length Characteristic Heating [Condition] Room temperature: 68°F (DBT) Operation condition: High fan speed Outdoor temperature: 47°F

Página 51

55 18. Exploded View and Replacement Parts List Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numb

Página 52

56 REF. NO. DESCRIPTION & NAME Q’TY CU-2E18NBU REMARK 1 BASE PAN ASS'Y 1 CWD52K1239A 2 SOUND-PROOF BOARD 1 CWH151230 3 FAN MOTO

Página 53

57 74 ACCESSORY CO. (DRAIN ELBOW) 1 CWG87C900 76 NUT - TERMINAL COVER 2 CWH7080300J 77 TERMINAL COVER 1 CWH171035 78 TUBE ASS'Y (L

Página 54

6 Item Unit OUTDOOR UNIT Air Volume High m3/min (ft3/min) 37.2 (1313) Refrigerant Control Device Expansion Valve Refrigerant Oil FV50S Ref

Página 55

7 Indoor unit combination Cooling Capacity (kW) Input Power (W) Outdoor Unit Operation Class (kW) Operation Mode Rating Min ~ Max Rating Min ~ Ma

Página 56

8 3. Dimensions

Página 57

9 4. Refrigeration Cycle Diagram